Daily maintenance knowledge of refrigerated dryer

Time:2017-07-20 Author:

冷冻式干燥机的日常维护保养知识

 

  

 

Daily maintenance knowledge of refrigerated dryer:

(1) the meter value of observation records in each class is 4 times

1. The pressure difference between inlet and outlet of compressed air shall not exceed 0.035Mpa;

2. Evaporation pressure gauge: 0.4mpa - 0.5mpa;

3. High pressure gauge 1.2mpa - 1.6mpa.

(2) the refrigerating dryer shall observe the drainage and sewage systems frequently

1. The float drain shall be cleaned once a week or so;

The blowpipe blows down once a week.

Cleaning method of the fraud electronic drainage device:

A. Close the ball valve in front of the automatic drain;

B. Loosen the upper fixed nut and take out the timing coil. During cleaning, the coil can never touch water, otherwise the coil will burn up.

C. Remove the hose, loosen the valve body of the drain, and empty the compressed air in the drain;

D. Remove the valve core and wipe clean;

E. Return the valve body to its original position, open the front ball valve slightly, and empty the impurities, water and oil in the drainage system with compressed air; Wipe the valve body with a cloth;

F. Install the valve core and timing coil in place; Install the hose again and open the front ball valve.

(3) observe the inlet temperature of cooling water system and compressed air system frequently

1, 2 ~ 32 ℃, cooling water temperature;

2. Water pressure: 0.15~ 0.3mpa;

3, compressed air inlet temperature should be 45 ℃ or less commonly, with hand touch it is advisable to intake pipe is not very hot), unless it is special.

4. The cooling water shall be kept clean, and the type Y filter shall be cleaned once every half month and the water quality shall be good once a month; The water condenser is cleaned once a year (depending on the water quality), and the air condenser is cleaned once a month.

Cleaning of the fluid coolant of the hull-tube type water condenser: close the cooling water inlet and outlet, open the end cover of the unconnected water pipe, and only clean the outer end cover and washer with water. Clean the inside of the copper pipe with gas, water or a stick with a cloth. Be careful not to use too much force when cleaning so as not to break the internal copper pipe.

Constantly observe the refrigeration system

1. The compressor should be touched by hand at least once a day.

2. The drying filter should touch the temperature difference between the two sides by hand every week, and the temperature difference should not be large (import heat and export cool need to be replaced);

3. If there is abnormal sound and heat in the compressor, please contact the after-sales service as soon as possible.

(5) check the electrical control system: blow and sweep dust, tighten the terminal (it must be carried out without charge)

(6) appearance maintenance

Wipe the surface of equipment with clean towel regularly oil, dust. Remove dust and oil stains from the floor of the air compressor and air dryer, and keep the environment clean.